Home >> Products >> ARMORED / UNARMORED POWER & CONTROL CABLES >>

No. of Cores

Nom. Thickness of PVC Insulation mm

Unarmoured Approx. Overall Dia mm

Armoured Nom. Steel Armour Size mm

Armoured Approx. Overall Dia. mm

Max.DC Conductor Resistance at 20° C   ohm/Km

AC Current Rating In Air GPPVC Insulation Amps

AC Current Rating In Air HRPVC Insulation Amps

AC Current Rating In Ground GPPVC Insulation Amps

AC Current Rating In Ground HRPVC Insulation Amps

2

0.8

12.6

1.4

14.4

12.1

20

24

23

27

3

0.8

13.0

1.4

15.0

12.1

17

21

21

24

4

0.8

13.5

1.4

15.5

12.1

17

21

21

24

5

0.8

14.5

1.4

16.0

12.1

14

17

17

19

6

0.8

14.6

1.4

17.0

12.1

13

16

15

18

7

0.8

14.6

1.4

17.0

12.1

12

15

14

17

9

0.8

18.0

1.4

19.0

12.1

12

14

14

16

10

0.8

18.6

1.4

20.5

12.1

11

13

13

15

12

0.8

18.6

4 X 0.8

19.7

12.1

10

12

12

14

14

0.8

20.0

4 X 0.8

20.5

12.1

10

12

11

13

16

0.8

22.0

4 X 0.8

21.5

12.1

9

11

11

12

19

0.8

23.0

4 X 0.8

22.6

12.1

9

10

10

12

24

0.8

26.0

4 X 0.8

25.6

12.1

8

10

9

11

27

0.8

27.0

4 X 0.8

26.0

12.1

8

9

9

10

30

0.8

27.0

4 X 0.8

26.9

12.1

7

9

9

10

37

0.8

28.0

4 X 0.8

28.6

12.1

7

8

8

9

44

0.8

32.0

4 X 0.8

32.0

12.1

6

7

7

8

52

0.8

33.0

4 X 0.8

33.0

12.1

6

7

7

8

61

0.8

35.0

4 X 0.8

34.5

12.1

6

7

6

7

All the above information and data are given purely as a guide. "Viral" is not responsible for any damages arising due to incorrect use.